Threeoutputsareprovidedasoutputprocessingfunctions:controloutput,SPoutputandaux-
iliaryoutput.
Control output
WhentheDCP31isselectedforuseasacontroller,controloutput
isoperational.Howoutputsareprocessedvariesaccordingtothe
outputtypesupportedonthemodel.
5G output
Over-range
READY mode
MANUAL mode
Current output 4 to 20mA (0 to 20mA)
Initialization of PID control
operation
PID control operation
Output change limitter
Output upper/lower limit limitter
Manipulated variable (MV1)
Output 1
AT execution
MV in READY mode
Preset manual value
Manual MV
MV at over-range
AT operation
Setting: Variable parameters 1 OUT/rp i d
Setting: PID parameters p/ 1 / d/8E
PID parameters dP/di /dd
PID parameters br
Setting: Variable parameters OTL
Setting: Variable parameter AT
Setting: PID parameters OL/OH
Setting: Setup data C 12/C 13
Setting: Setup data C 14/C 15
Setting: Setup data C 16
5-24
Chapter 5. FUNCTIONS
5 - 6 Output Processing Functions