WARNING
Before removing, mounting, or wiring the DCP31, be sure to turn off the power to
the DCP31 and all connected devices.
Failure to do so might cause electric shock.
Relay output (0D)
Connectasfollows:
Handling Precautions
When switching small currents, connect a bleeder resistor to allow
current flow of the minimum relay switching input (100mA min.).
Current output (5G)
Connectasfollows:
Handling Precautions
4 to 20mAdc and 0 to 20mAdc can be selected in setup data
C
9
0
.
11
12
13
Load
Power supply
Contact rating, resistive load
5A (30 Vdc/120 Vac)
4A (240 Vac)
Minimum switching current: 100 mA
11
12
13
Actuator
4 to 20/0 to 20 mAdc
Resistive load 600 Ω max.