3-2
Chapter 3. MOUNTING
3 - 2  Panel Cutout Dimensions
Panelcutoutdimensions
Useasteelpanelofatleast2mminthicknessformountingthecontroller.
 Handling Precautions
• When mounting the controller, take care to prevent the tempera-
ture at the lower surface of the controller’s case from exceeding 
the operating temperature range (0 to 50°C), particularly when 
mounting vertically or during multiple mounting.
46 4696 x (N - 1)
96 x N - 4
N=number of units installed
Panel cutout dimensions
Panel cutout dimensions during multiple mounted 
(recommended)
150min.(when vertically mounted)
99 min. (when horizontally mounted)
(107 min. when hard dust-prevention 
cover is used)
Panel cutout dimensions when mounting units horizontally and vertically (recommended)
92
+ 0. 8
 0
92
+ 0. 8
 0
92
+ 0. 8
 0