7-39
Chapter 7. PARAMETER SETUP
PID parameter settings
P
I
d
No. Item Code Item
Factory
Setting
User
Setting
Setting
1
P
-1
Proportional band
(PID set 1)
100.0
P
: 0.0 to 999.9% (
0D, 6D output models
)
0.0 enables ON-OFF control.
0.1 to 999.9% (models other than
0D and 6D output models)
I
: 0 to 3600s
0 disables integrating action.
D
: 0 to 1200s
0 disables derivative action.
O
L
: -10.0 to MV upper limit %
O
H
: MV lower limit to 110.0%
R
E
: 0.0 to 100.0%
B
R
: 0 to 30
0 disables the brake function.
D
P
: 0.1 to 999.9%
D
1
: 1 to 3600s
D
D
: 0 to 1200
0 disables derivative action.
[Note]
• On0Dand6Doutputmodels,when
P
setting is 0.0, ON-OFF control is
enabled. “– – – –” is displayed for items
I
,
D
,
O
L
,
O
H
,
R
E
,
D
P
,
D
I
and
D
D
, and
setting is not possible.
• Whenvariableparameter
.
-C
setting
is 2 (estimated position control only) on
2G output models, “– – – –” is displayed
for items
O
L
and
O
H
, and setting is not
possible.
• When
I
setting is not 0, “– – – –” is
displayed for
R
E
and setting is not
possible.
• Whenvariableparameter
S
T
setting
is 0 (smart-tuning disabled), “– – – –”
is displayed for
B
R
and setting is not
possible.
• Whenvariableparameter
2
P
1
D
setting is 0 (2 degrees of freedom PID
disabled), the items for
D
P
,
D
1
,
D
D
are
not displayed.
2
1
-1
Reset time
(PID set 1)
0
3
D
-1
Rate time
(PID set 1)
0
4
O
L
-1
MV lower limit
(PID set 1)
0.0
5
O
H
-1
MV upper limit
(PID set 1)
100.0
6
R
E
-1
Manual reset
(PID set 1)
50.0
7
D
R
-1
Brake
(PID set 1)
0
8
D
P
-1
Disturbance inhibit
proportional band
(PID set 1)
100.0
9
D
1
-1
Disturbance inhibit
reset time
(PID set 1)
120
10
D
D
-1
Disturbance inhibit
rate time
(PID set 1)
0
11
P
-2
Proportional band
(PID set 2)
100.0
12
1
-2
Reset time
(PID set 2)
0
13
D
-2
Rate time
(PID set 2)
0
14
O
L
-2
MV lower limit
(PID set 2)
0.0
15
O
H
-2
MV upper limit
(PID set 2)
100.0
16
R
E
-2
Manual reset
(PID set 2)
50.0
17
B
R
-2
Brake
(PID set 2)
0