EasyManua.ls Logo

Azbil DCP31 - 5 - 2 Program Patterns

Azbil DCP31
242 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Patterns
SPandtimecomprisethesettingsforasinglesegmentinapattern.
Upto30segmentscanbelinkedtocreateabroken-linewhoseverti-
calaxisisSPandhorizontalaxisistime.
Thissystemiscalledthe“RAMP-X”system.
SPsetting: WithinrangeofSPlimitterupperandlowerlimits
Timesetting: 0to99h,59minor0to99min,59s
(SelectthetimeunitinsetupdataC64.)
SPisthepointthatcorrespondstothetimeelapsedinthecurrent
segmentonastraightlinemadebyjointingthestartpoint(SPset-
tingvalueoftheprevioussegment)toanendpoint(SPsettingvalue
ofthecurrentsegment).
Accordingly,segmentsarecategorizedasfollows:
• Risingramp(risingramp,risingtendency)
PrevioussegmentSPsettingvalue<currentsegmentSPsetting
value
• Fallingramp(fallingramp,fallingtendency)
PrevioussegmentSPsettingvalue>currentsegmentSPsetting
value
• Soak(soak)
PrevioussegmentSPsettingvalue=currentsegmentSPsetting
value
InthecaseoftheNo.1segment,boththestartandendpointsbe-
comethesoaksegmentoftheNo.1segmentSPsettingvalues.
SP(otherthanNo.1segment)iscalculatedasbythefollowing
formula:
SP=(currentsegmentSPsettingvalue-previoussegmentSPsetting
value)x(currentsegmentelapsedtime÷currentsegmenttime
setting)+previoussegmentSPsetting+SPbias*
*SPbiasiscommonlyeffectiveinallprogramsandallsegments.
Time setting of current segment
SP setting value of
current segment
SP setting value of
previous segment
5-2
Chapter 5. FUNCTIONS
5 - 2 Program Patterns

Table of Contents

Related product manuals