Item Specification
Program Number of programs 19
Number of segments 30 per program
Segment setting system RAMP-X system: Set by set points (SP) and time.
Segment time 0 to 99h 59min, 0 to 99min 59s, or 0.0 to 599.9s (time unit selectable)
Basic time accuracy ±0.01% (0.1s delay when segment time setting=0)
Events (3) Set operating point.
Time events (5) Set ON and OFF times.
PID set No. Set 0 to 8 (Set 0 for continuation of previous segment) (Set 0 to 4 on
heat/cool models.)
G.Soak Sets G.Soak width 0 to 1000U.
PV start Sets program ON/OFF.
Cycle Sets program count 0 to 9999.
Pattern link Sets program No.0 to 19 (0: no link)
Tag Sets 8 alphanumerics for each program (not displayed on controller)
Input Input type Thermocouple: K, E, J, T, B, R, S (JIS C 1602-1981)
WRe5-26 (Hoskins Data)
PR40-20 (Johnson Matthey Data)
Ni·NiMo (General electric Data)
N (N.B.S. Monograph 161)
PLII (Engelhard Industries Data (IPTS68))
DIN U, DIN L (DIN 43710-1985)
Gold iron chromel (Hayashidenko Data)
Resistance temperature detector (RTD):
Pt100, JPt100 (JIS C 1604-1989)
DC current: 4 to 20mA, 0 to 20 mA, 0 to 10mA
DC voltage: −10 to +10mV, 0 to 100mV, 0 to 1V, −1 to +1V, 1 to 5V,
0 to 5V, 0 to 10V
Multi-range of thermocouple, resistance temperature detector,
DCvoltage, and DC current (see page 2-8, 2-9).
Input readout accuracy ±0.1%FS ±1U (varies according to standard conditions, display value
conversion and range)
• For the K44, K46, and T44 thermocouples at –100°C and colder:
±1°C±1U
• At 260°C max. of B thermocouple: ±4%FS ±1U
At 260 to 800°C: ±0.4%FS ±1U
At 800 to 1800°C: ±0.2%FS ±1U
• At 100°C max. of R and S thermocouples: ±0.2%FS ±1U
At 100 to 1600°C: ±0.15%FS ±1U
• At 300°C max. of PR40-20 thermocouple: ±2.5%FS ±1U
At 300 to 800°C: ±1.5%FS ±1U
At 800 to 1900°C: ±0.5%FS ±1U
• Golden iron chromel thermocouple: ±1.5K ±1U
• Range of F01, F33, F38, P01, P33 and P38 of RTD input: ±0.15%FS ±1U
• At 0 to 10mV range: ±0.15%FS ±1U
• At −100°C max. of DIN U thermocouple: ±2°C ±1U
At −100 to 0°C: ±1°C ±1U
• At −100°C max. of DIN L thermocouple: ±1.5°C ±1U