7-66
Chapter 7. PARAMETER SETUP
Constant-value operation data settings
C
N
S
t
No. Item Code Item
Factory
Setting
User
Setting
Setting
1
.O
D
E
Operation mode 0 0: Program operation
1: Constant-value operation
[Note]
This setting can be changed only in
the READY mode.
2
S
P
SP1 0 This setting can be set in the SP1 lower to
upper limit range in setup data settings
C
0
9
and
C
1
0
.
3
S
P
2
Unused 0 [Note]
“– – – –” is displayed and setting is not
possible.
4
E
V
1
Event 1 setting value 9999 -1999 to 9999U (event type is deviation or SP)
0 to 9999U (event type is absolute value
deviation)
-10.0 to 110.0% (event type is MV or MFB)
[Note]
When the event conguration data
type setting is ≥ 50 for each event,
“– – – –” is displayed and setting is not
possible.
5
E
V
2
Event 2 setting value 9999
6
E
V
3
Event 3 setting value 9999
7 Unused [Note]
“– – – –” is displayed and setting is not
possible.
8 Unused
9 Unused
10 Unused