7-67
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory
Setting
User
Setting
Setting
11
P
.
Proportional band
(CH1)
100.0
P
: 0.0 to 999.9% (0D, 6D output models)
0.0 enables ON-OFF control.
0.1 to 999.9% (models other than
0D and 6D models)
I
: 0 to 3600s
0 disables integral action.
D
: 0 to 1200s
0 disables derivative action.
O
L
: -10.0 to MV upper limit %
O
H
: MV lower limit to 110.0%
R
E
: 0.0 to 100.0%
B
R
: 0 to 30
0 disables the brake function.
D
P
: 0.1 to 999.9%
D
1
: 1 to 3600s
D
D
: 0 to 1200
0 disables derivative action.
[Note]
• On0Dand6Doutputmodels,when
P setting is 0.0, ON-OFF control is
enabled. “– – – –” is displayed for items
I
,
D
,
O
L
,
O
H
,
R
E
,
D
P
,
D
I
and
D
D
, and
setting is not possible.
• Whenvariableparameter
.
-C
setting
is 2 (estimated position control only) on
2G output models, “– – – –” is displayed
for items
O
L
and
O
H
, and setting is not
possible.
• When
I
setting is not 0, “– – – –” is
displayed for
R
E
and setting is not
possible.
• Whenvariableparameter
S
T
setting
is 0 (smart-tuning disabled), “– – – –”
is displayed for
B
R
and setting is not
possible.
• Whenvariableparameter
2
P
1
D
setting is 0 (2 degrees of freedom PID
disabled), the items for
D
P
,
D
1
,
D
D
are
not displayed.
For details, see the Note for PID param-
eters.
12
I
.
Reset time (CH1) 0
13
D
.
Rate time (CH1) 0
14
O
L
.
MV lower limit (CH1) 0.0
15
O
H
.
MV upper limit (CH1) 100.0
16
R
E
.
Manual reset (CH1) 50.0
17
B
R
.
Brake (CH1) 0
18
D
P
.
Disturbance inhibit
proportional band
(CH1)
100.0
19
D
I
.
Disturbance inhibit
reset time (CH1)
120
20
D
D
.
Disturbance inhibit
rate time (CH1)
0
21
P
.-C
Proportional band
(for cool control)
100.0
22
I
.-C
Reset time (CH1) (for
cool control)
0
23
D
.-C
Rate time (CH1) (for
cool control)
0
24
O
L
.-C
MV lower limit (CH1)
(for cool control)
0.0
25
O
H
.-C
MV upper limit (CH1)
(for cool control)
100.0
26
R
E
.-C
Manual reset (CH1)
(for cool control)
50.0