8-10
Chapter 8. PROGRAM SETUP
themodechangestotheENDmodeatsegmentswhoseONtime
andpatternitemtimeareequal.
When event type is controller status event
Inthiscase,theeventitemontheprogrammingmapisskippedand
notdisplayed.
Setting up time events 1 to 5
(1) Inthesettingdisplaystate,movetotheevent1to5itemsofthe
segmenttobesetupontheprogrammingmap.
(2) Ifyoupress
ENT
,theupperdisplaystartsblinkingtoindicate
startofentrytotheNo.1setup.
(3) Press
, , or tosettotheNo.1setupONtime
setting.
Settingrange: 0:00to99:59(h:min/min:s)
0.0to599.9(0.1s)
(Selecteitherofh:minormin:sasthetimeunitinsetupdata
C64
.“:”issubstitutedby“.”asitcannotbedisplayed.)
(4) Whenyoupress
ENT
,blinkingontheupperdisplaystops.The
lowerdisplaythenstartsblinkingtoindicatestartofentrytothe
No.2setup.
( W h e n
FUNC
+
CLR
arepressed,theupperandlowerdisplays
bothreturnto“----”andblinkingstops.)
(5) Press
, , or totheNo.2setupONtimeset-
ting.
Settingrange: ONtimesetting+0:01to99:59(h:min/min:s)
ONtimesetting+0.1to599.9(0.1s)
(6) Whenyoupress
ENT
,blinkingontheupperdisplaystops.
( W h e n
FUNC
+
CLR
arepressed,theupperdisplayreturnsto
“----”andstopsblinking.)
Display
•“----”isdisplayedforthesettingvaluesinnon-setsegments.
•Onmodelsthatdonotsupporttimeevents,event1to5itemson
ON time setting value
OFF time setting value
Program No. Segment No.
Pattern
tendency
LEDs corresponding to T1 to T5 lit.