TheDCP31isnotequippedwithapowerswitchorprotectivefuses.Ifnecessary,preparethese
externally.
Whenavoltageof90to264Vacisappliedacrossterminals
and ontheDCP31,display
appearsforabout10safterwhichcontrolandotheroperationsarestarted.Duringcontroller
startupuntilstartofoperations,theLEDsontheprofiledisplaylightsuccessivelyatunevenin-
tervalsclockwisefromtopright.Thefollowingdiagramshowstheflowofoperationsatstartup:
Startup flow
Handling Precautions
With the following modes and items, the state when the power is
turned OFF continues when the power is turned back ON.
• READY, RUN, HOLD, FAST, END modes
• AUTO, MANUAL modes
• MANUAL values in MANUAL mode
• Program No., segment No.
• Progress time in segment
• Display No. if in basic display state in AUTO mode
Power ON
NO
YES
Start of operations
Check start of general reset
Press key.
RAM backup normal?
ENT
Continuation of program operation/constant-value operation
modes
Continuation of READY/RUN/HOLD/FAST/END modes
Continuation of AUTO/MANUAL modes
(Continuation of manual value if in MANUAL mode)
Continuation of program No./segment No.
Continuation of segment progress time
Continuation of display No. of basic display state in AUTO mode
Parameter=factory shipment setting
Delete entire program.
Program operation mode
READY mode
AUTO mode
Program No.1=1/segment No.=1
Segment progress time=0
Cancellation of auto-tuning/smart-tuning
Cancellation of MFB automatic adjustment by 2G output
Initialization of G.Soak standby time
Initialization of PID operation
Initialization of event output state
Setting display state Æ Basic display state
Display No. of basic display state in MANUAL mode
6-1
Chapter 6. OPERATION
6 - 1 Turning the Power ON