8-12
Chapter 8. PROGRAM SETUP
When event type is PV type event
(1) Inthesettingdisplaystate,movetotheevent1to5itemsofthe
segmenttobesetupontheprogrammingmap.
(2) Ifyoupress
ENT
,theupperdisplaystartsblinkingtoindicate
startofentrytotheNo.1setup.
(3) Press
, , or tosettotheNo.1setupevent
operatingpointsetting.
Settingrange: -1999to+9999U
0to9999U(incaseofabsolutevaluedeviation
event)
-10.0to+110.0%(incaseofMV,MFBevent)
(4) Whenyoupress
ENT
,blinkingontheupperdisplaystops.
( W h e n
FUNC
+
CLR
arepressed,theupperdisplayreturnsto
“----”andstopsblinking.)
Display (PV type event)
•“----”isdisplayedforthesettingvaluesinnon-setsegments.
•Whensetupdata
C68
issetto1,event1to5itemsonthepro-
grammingmapareskippedandnotdisplayed.
When event type is a controller event
Theeventitemontheprogrammingmapisskippedandnotdis-
played.
Upper display
Program No. Segment No.
Pattern
tendency
LEDs corresponding to T1 to T5 lit.