7-11
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory 
Setting
User 
Setting
Setting
23
C
 
Y
 
.
 
2
Output 2 time 
proportional output 
cycle
10 5 to 120s (relay output)
1 to 60s (voltage output)
[Note]
   On models whose output 2 is neither 
relay output nor voltage output,  
“– – – –” is displayed and setting is not 
possible.
24
C
 
Y
 
.
 
3
Unused – [Note]
   “– – – –” is displayed and setting is not 
possible.
25
d
 
V
 
-L
3-position control 
deviation lower limit
5U 0 to 1000U
[Note]
   On models other than 3D output mod-
els, “– – – –” is displayed and setting is 
not possible.
26
d
 
V
 
-h
3-position control 
deviation upper limit
5U
27
H
 
Y
 
-L
3-position control 
lower limit hysteresis
5U
28
H
 
Y
 
-H
3-position control 
upper limit hysteresis
5U
29
 
.-C
Motor control 
method selection
0 0:   MFB control (conventional) + estimat-
ed position control
1:   MFB control (conventional) only
2:   Estimated position control only
[Note]
   On models other than 2G output mod-
els, “– – – –” is displayed and setting is 
not possible.
30
 
.-A
 
t
Motor valve opening 
automatic adjust-
ment
0 0:  Adjustment disabled
1:  Adjustment enabled
[Note]
   On models other than 2G output mod-
els, “– – – –” is displayed and setting is 
not possible.
   On 2G output models, when 
 
.-C
 
setting is 2, “– – – –” is displayed and 
setting is not possible.