7-10
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory
Setting
User
Setting
Setting
16
C
P
.
1
4
PID auto-switching
point 1-4
600U -1999 to +9999U
[Note]
On heat/cool models, “– – – –” is dis-
played and setting is not possible.
On other models, when setup data
C
1
1
setting is 0 (PID set auto-switching
OFF), “– – – –” is displayed and setting
is not possible.
17
C
P
.
1
5
PID auto-switching
point 1-5
800U
18
C
P
.
1
6
PID auto-switching
point 1-6
1000U
19
C
P
.
1
7
PID auto-switching
point 1-7
1200U
20
F
A
S
T
FAST factor 0 0: 2X
1: 10X
2: 60X (10X)
3: 120X (10X)
[Note]
When setup data
C
6
4
setting is 1
(program time unit:min/s), the FAST
factor is 10X for settings 2 and 3.
21
d
i
f
f
ON-OFF control
dierential
5U 0 to 1000U
[Note]
This setting is displayed on 0D and 6D
models.
Position-proportion-
al dead zone
5.0 0.5 to 25.0%
[Note]
This setting is displayed on 2G output
models.
Heat/cool control
dead zone
0.0 -100.0 to +50.0%
[Note]
This setting is displayed on heat/cool
models.
[Note]
On 5G output models, “– – – –” is dis-
played and setting is not possible.
22
C
Y
.
1
Output 1 time
proportional output
cycle
10 5 to 120s (relay output)
1 to 60s (voltage output)
[Note]
On models whose output 1 is neither
relay output nor voltage output,
“– – – –” is displayed and setting is not
possible.