7-13
Chapter 7. PARAMETER SETUP
•When
LOC
issetto3,thefollowingkeysaredisabled.
Basicdisplaystate:
PROG
(programselection)
(programselection)
RUN/HOLD
(RUN,HOLD)
PROG
+
RUN/HOLD
(RESET)
PROG
+
DISP
(ADV)
FUNC
+ (FAST)
A/M
(AUTO,MANUAL)
AT
(ATstart,ATcancel)
FUNC
+
CLR
+
DISP
(generalreset)
However,notethatMV(whencontrollerfunctionsareselected)and
SP(whenprogrammerfunctionsareselected)canbechangedinthe
basicdisplaystateintheMANUALmode.
•When
LOC
issetto4,allkeysdisabledwhen
LOC
issetto2and3
aredisabled.
P
R
T
C
(program protect)
0: Changingprogramsettingsenabled
1: Changingprogramsettingsdisabled
When
PRTC
issetto1,thefollowingkeysaredisabled.
Basicdisplaystate:
+
PROG
(programcopy)
FUNC
+
CLR
+
DISP
(generalreset)
Programsetupstate:
ENT
(startofvalueentry)
FUNC
+
ENT
(segmentinsert/delete)
O
T
L
(MV change limit)
TheMVisincreasedordecreasedbythesamevaluesothatthe
outputchangeistakenasthelimitsettingvaluewhentheoutput
change(%)afterPIDoperationisgreaterthanthislimitsetting.
ThebelowexampleshowstheactualchangeinMVwhentheMV
changesfrom20%to22%withthechangelimitsettingat0.5%.
MVisoutputat0.5%settingvalueincrementsevery0.1s,and
reaches22%in0.4s.
%
22
21
20
t t + 0.1 t + 0.2 t + 0.3 t + 0.4
s