7-48
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory
Setting
User
Setting
Setting
45
C
4
5
3-position control 0 0: 3-position control disabled
1: 3-position control enabled
[Note]
On models not supporting 3D output,
“– – – –” is displayed and setting is not
possible.
46
C
4
6
Auxiliary output 1
type
0 0: PV1
1: SP1
2: Deviation1
3: MV1
4 to 7: NOP
8: MFB
9 to 11: NOP
[Note]
On models not supporting auxiliary
output 1, “– – – –” is displayed and set-
ting is not possible.
When set to NOP (or to MFB on models
other than 2G output models), output
is xed to 4mA.
When set to SP or deviation, output in
the READY mode is xed to 4mA.
47
C
4
7
Auxiliary output 1
lower limit (4mA)
0 -1999 to +9999U
-199.9 to +999.9%
[Note]
When the auxiliary output type is MV
or MFB, the unit is %. Otherwise, the
unit is U.
48
C
4
8
Auxiliary output 1
upper limit (20mA)
1000
49
C
4
9
Auxiliary output 2
type
0 0: PV1
1: SP1
2: Deviation1
3: MV1
4 to 7: NOP
8: MFB
9 to 11: NOP
[Note]
When auxiliary output 2 is not sup-
ported, “– – – –” is displayed and set-
ting is not possible.
When set to NOP (or to MFB on models
other than 2G output models), output
is xed to 4mA.
When set to SP or deviation, output in
the READY mode is xed to 4mA.