7-48
Chapter 7. PARAMETER SETUP
No. Item Code Item
Factory
Setting
User
Setting
Setting
45
C
4
5
3-position control 0 0: 3-position control disabled
1: 3-position control enabled
[Note]
On models not supporting 3D output,
“– – – –” is displayed and setting is not
possible.
46
C
4
6
Auxiliary output 1
type
0 0: PV1
1: SP1
2: Deviation1
3: MV1
4 to 7: NOP
8: MFB
9 to 11: NOP
[Note]
On models not supporting auxiliary
output 1, “– – – –” is displayed and set-
ting is not possible.
When set to NOP (or to MFB on models
other than 2G output models), output
is xed to 4mA.
When set to SP or deviation, output in
the READY mode is xed to 4mA.
47
C
4
7
Auxiliary output 1
lower limit (4mA)
0 -1999 to +9999U
-199.9 to +999.9%
[Note]
When the auxiliary output type is MV
or MFB, the unit is %. Otherwise, the
unit is U.
48
C
4
8
Auxiliary output 1
upper limit (20mA)
1000
49
C
4
9
Auxiliary output 2
type
0 0: PV1
1: SP1
2: Deviation1
3: MV1
4 to 7: NOP
8: MFB
9 to 11: NOP
[Note]
When auxiliary output 2 is not sup-
ported, “– – – –” is displayed and set-
ting is not possible.
When set to NOP (or to MFB on models
other than 2G output models), output
is xed to 4mA.
When set to SP or deviation, output in
the READY mode is xed to 4mA.