7-55
Chapter 7. PARAMETER SETUP
C
4
7
(auxiliary output 1 lower limit)
C
4
8
(auxiliary output 1 upper limit)
C
5
0
(auxiliary output 2 lower limit)
C
5
1
(auxiliary output 2 upper limit)
•Thisisthescalingsettingforauxiliaryoutput.Thevaluesofthe
upperlimitsettingandlowerlimitsettingcanalsobeinverted.
•Inthefollowingexample,thetypeissettoMVatauxiliaryinput
1.12mAisoutputwhenMVis100%and20mAisoutputwhen
MVis0%.Inthefollowingfigure,MVis200%whenvirtually
calculatedat4mA.
Accordingly,thesettingof
C47
and
C48
become200.0and0.0,
respectively.
C
6
5
(time display)
0: Remainingsegmenttime
1: Totaloperationtime
•Thisselectsthetimedisplayinthebasicdisplaystateinthepro-
gramoperationmode.
•Whensetto0,intheREADYmode,thetimesettingvalueofthe
currentlyselectedsegmentisdisplayed.
•Whensetto0,intheRUN,HOLD,FASTorENDmodes,the
remainingtimeforthecurrentlyexecutingsegmentisdisplayed
afterbeingroundeddown.
Forexample,iftheremainingtimeis1h,30min,59swhenthe
timeunitissetto“h:min,thetimedisplayis“
1.30
”.
•Whensetto1,intheREADYmode,thetimedisplayis“
0.00
”.
•Whensetto1,intheRUN,HOLD,FASTorENDmodes,thetime
ittakestoshiftfromtheREADYtotheRUNmodeisdisplayed
afterbeingrounddown.Also,after“
99.59
”thetimedisplay
changesto“
0.00
”.
Forexample,iftheremainingtimeis101h,30min,59swhenthe
totaloperationtimeissetto“h:min”,thetimedisplayis“
1.30
”.
•IntheFASTmode,thetimedisplaychangesaccordingtothe
FASTscaleifthisparameterissettoeither0or1.
MV
4 mA
12 mA
20 mA
200 %100 %
Auxiliary output 1