11-3
Chapter 11. SPECIFICATIONS
Item Specification
External 
Switch 
(RSW) 
Input
Number of inputs 12
Types of connectable 
outputs
Dry contacts (relay contact) and open-collector (current sink to ground)
Terminal voltage (open) 10.4 to 12.6V (under operating conditions) across common terminal 
(terminal 
 ) and each input terminal
Terminal current 
(shortcircuit)
5.0 to 6.6mA across each terminal (under operating conditions)
Allowable contact 
resistance (dry contact)
ON:  700Ω max. (under operating conditions)
OFF:  10kΩ min. (under operating conditions)
Residual current 
(allowable open-
collector ON)
3V max. (under operating conditions)
Leakage current 
(allowable open-
collector OFF)
0.1mA max. (under operating conditions)
Parallel connection to 
other instruments
Can be connected to Azbil Corporation SDC40 and DCP30 series.
Assignments (fixed) RUN, HOLD, RESET, ADV, program No.
Assignments (variable) FAST, PV start, AT, AUTO/MANUAL, G.Soak cancel, reverse/direct action
Input sampling cycle 0.1s
ON detection min. hold 
time
0.2s (program No. 0.4s)
Indica-
tion/
Program-
mer
Upper display Green 4-digit, 7-segment LED
This normally displays PV values. Item codes are displayed in parameter 
setup.
Lower display Orange 4-digit, 7-segment LED
This normally displays SP values. Setting values are displayed in param-
eter setup.
Program No. display Green 2-digit, 7-segment LED
This normally displays program No.
Segment No. display Green 2-digit, 7-segment LED
This normally displays segment No. Item Nos. are displayed in parameter 
setup, and alarm No. is displayed when alarm occurs.
Profile display 6 orange LEDs
Displays program pattern rise, soak and fall tendencies.
Status displays 22 round LEDs
Modes:  RUN, HLD, MAN, PRG (green)
Display details:  PV, SP, OUT, TM, CYC (green)
Battery voltage:  BAT (red) (blinks at low voltage)
Status:  AT, OT1, OT2, OT3 (orange)
Events:  EV1, EV2, EV3, T1, T2, T3, T4, T5 (orange)
Operation keys 13 rubber keys
Loader connector port 1 (dedicated cable with stereo mini plugs)