11-8
Chapter 11. SPECIFICATIONS
Item Specification
General
Specifica-
tions
Memory backup Memory Battery backed-up RAM
Battery life Controller power OFF Approx. 3 years under standard
conditions
Controller power ON Approx. 10 years under standard
conditions
Rated power supply
voltage
100 to 240Vac, 50/60Hz
Allowable power supply
voltage
90 to 264Vac, 50/60Hz
Power consumption 30VA max.
Power ON rush current 30A max., 10ms (under operating conditions)
Handling Precautions
When starting up a number of DCP31s simultaneously, ensure ample
power is supplied or stagger startup times. Otherwise, the controllers
may not start normally due to inrush current induced-voltage drop.
Voltage must stabilize within 2s after power ON.
Power ON operation Reset time: 15s max. (time until normal operation possible under
normal operating conditions)
Allowable transient
power loss
20ms max. (under operating conditions)
Insulation resistance Min. 20MΩ across power terminal (1) or (2) and ground terminal (3)
(using a 500Vdc megger)
Dielectric strength
1500Vac 50/60Hz for 1min across power terminal and ground terminal
1500Vac 50/60Hz for 1min across relay output and ground terminal
500Vac 50/60Hz for 1min across non-power terminal and ground terminal
500Vac 50/60Hz for 1min across isolated terminals
Standard conditions Ambient
temperature
23 ±2°C
Ambient humidity 60 ±5%RH
Rated power
supply voltage
105 Vac ±1%
Power frequency 50 ±1Hz or 60 ±1Hz
Vibration resistance
0m/s
2
Impact resistance 0m/s
2
Mounting angle Reference plane (vertical) ±3°
Operating conditions Ambient
temperature range
0 to 50°C (temperature at case bottom when
closely mounted)
Ambient humidity
range
10 to 90%RH (without condensation)
Rated power supply
voltage
100 to 240Vac
Power frequency 50 ±2Hz or 60 ±2Hz
Vibration resistance 0 to 1.96m/s
2
Impact resistance 0 to 9.80m/s
2
Mounting angle Reference plane (vertical) ±10°
Altitude 2000m max.