4-2
Chapter 4. WIRING
 Handling Precautions
• Before wiring the DCP31, check the controller catalog No. and 
terminal Nos. on the label on the rear of the body. After wiring 
the DCP31, be sure to check the wiring for any mistakes.
• Maintain a distance of at least 50 cm between I/O leads or com-
munications leads and the power lead. Also, do not pass these 
leads through the same piping or wiring duct.
• When wiring with crimped terminals, take care to prevent con-
tact with adjacent terminals.
• When connecting the DCP31’s thermocouples in parallel to other 
controllers, make sure that the total input impedance of the 
other controller is at least 1MΩ. 
If the input impedance is less than 1MΩ, the DCP31 may not be 
able to detect sensor disconnection.
• When inputting the DCP31’s I/O (parallel connection in case of 
input) to an A/D converter or analog scanner, read data may 
fluctuate. 
To prevent this, adopt one of the following measures.
(1) Use a low-speed, integrating type A/D converter.
(2)   Insert an isolator without a switching power supply between 
the DCP31 and A/D converter.
(3) Average data on a personal computer when reading data.
(4) If possible, set a filter for the input.
• Provide the wiring for the instrument power supply with a mains 
power shutoff switch within reach of the instrument operator.
• Provide a delay-type (T) rated current 1A and rated voltage 250 V 
fuse on the instrumentation power supply wiring. Connect to live 
conductor. (IEC 127)
• Devices and systems to be connected to this unit must have 
reinforced insulation or double insulation sufficient to withstand 
the maximum operating voltage levels of the power supply and 
input/output parts.
• Do not connect 3 crimp terminals or more to the same terminal 
screw.