5-9
Chapter 5. FUNCTIONS
 However,ONandOFFtimessetforseg-
mentendpointswhentheENDmodeis
shiftedtoarevalid.
(Seesegment9inthefigure,andcom-
parewithsegment10intheENDmode.)
• WhentheONtimeissetto0(noOFF
timesetting,orOFFtimeisgreaterthan
0),outputbecomesOFFattime0.
 Ifoutputattheprevioussegmentend
pointwasONatthistime,theoutput
statusatthesegmentswitchingpoint
doesnotmomentarilybecomeOFF.
(Seesegments5and6inthefigure.)
• TheG.Soakstandbytimeisnotincluded
intheONandOFFtimes.
(Seesegment7inthefigure.)
• IftheONtimeissetto0inthecaseof
G.Soakstandby,outputbecomesON
fromtheG.Soakstandbystate,andthe
ONtimeisstartedatcompletionofthe
G.Soakstandbytime.
 Theoutputtime=G.Soaktime+OFF
time
(Seesegment8inthefigure.)
• ONandOFFtimesettingsthesametime
asthesegmentendpointarevalidinthe
caseofthefinalsegmentENDmode.
(Seesegment10inthefigure.)
Segment 5 6
ON time
OFF time
Output ON
Output OFF
ON 
continued
G.Soak standby
ON
=
0
Segment 7
ON time
OFF time
Output ON
Output OFF
Segment time start
Segment 8
ON time
OFF time
Output ON
Output OFF
G.Soak standby
Segment 9
ON time
OFF time
Output ON
Output OFF
ON
=
segment time
Segment 10
Segment time
ON time
OFF time
Output ON
Output OFF
END mode
ON
=
segment time
Segment 8 time start
When 0N
=
0, output turns 
ON when there is input to
segment 8.