5.7 SCHEDULER
The controller contains an inbuilt exercise run scheduler, capable of automatically starting and
stopping the set. Up to 16 scheduled start/stop sequences can be configured to repeat on a 7-day or
28-day cycle. Scheduled runs may be island, off load or parallel depending upon module
configuration.
Example
Screen capture from DSE
Configuration Suite Software
showing the configuration of
the Exercise Scheduler.
In this example the start
request is made on Monday in
the Second Week of each
month at 09:00 am and lasts
for 5 hours, then Wednesday
in the Third Week of each
month at 13:30 pm and lasts
for 30 minutes.
5.7.1 STOP/RESET MODE
• Scheduled runs do not occur when the module is in Stop/Reset Mode .
5.7.2 MANUAL MODE
• Scheduled runs do not occur when the module is in Manual Mode waiting for a start
request.
• If a scheduled run configured to ‘Parallel’ or ‘Island’ begins when the module is in Manual
Mode , generator bus is available and off load, the generator bus is placed into the
appropriate state.