9 FAULT FINDING
NOTE: The below fault finding is provided as a guide check-list only. As the module can
be configured to provide a wide range of different features, always refer to the source of the
module configuration if in doubt.
9.1 STARTING
Unit is inoperative
Read/Write configuration
does not operate
Check:
• The battery and wiring to the unit.
• The DC supply.
• The DC fuse.
Unit shuts down
Check:
• DC supply voltage is not above 35 V or below 9 V
• The operating temperature is not above 70 °C.
• The DC fuse.
Fail to Start is activated on
DSE8x10 after pre-set
number of attempts to start
Check:
• Wiring of fuel solenoid.
• Fuel supply.
• Battery supply.
• Battery supply is present on the Fuel output of the module.
• The speed-sensing signal is present on the module’s inputs.
Refer to engine manual.
Continuous starting of
generator when in
Auto Mode .
Check:
• That there is no signal present on the “Remote Start” input.
• Input polarity is correct correctly.
• The mains supply is available and within configured limits
Generator fail to start on
receipt of Remote Start
signal.
Check:
• Start Delay timer has timed out.
• Signal is on “Remote Start” input. Confirm correct
configuration of input is configured to be used as “Remote
Start”.
• MSC link operation
• The DSE8661 and DSE8x10 modules are in Auto Mode .