Fault Finding
057-259 ISSUE: 1 Page 138 of 146
9 FAULT FINDING
NOTE: The below fault finding is provided as a guide check-list only. As the module can
be configured to provide a wide range of different features, always refer to the source of the
module configuration if in doubt.
9.1 STARTING
Symptom
Possible
Remedy
Unit is inoperative
Read/Write configuration
does not operate
Check:
The battery and wiring to the unit.
The DC supply.
The DC fuse.
Unit shuts down
Check:
DC supply voltage is not above 35 V or below 9 V
The operating temperature is not above 70 °C.
The DC fuse.
Fail to Start is activated on
DSE8x10 after pre-set
number of attempts to start
Check:
Wiring of fuel solenoid.
Fuel supply.
Battery supply.
Battery supply is present on the Fuel output of the module.
The speed-sensing signal is present on the module’s inputs.
Refer to engine manual.
Continuous starting of
generator when in
Auto Mode .
Check:
That there is no signal present on the “Remote Start” input.
Input polarity is correct correctly.
The mains supply is available and within configured limits
Generator fail to start on
receipt of Remote Start
signal.
Check:
Start Delay timer has timed out.
Signal is on “Remote Start” input. Confirm correct
configuration of input is configured to be used as “Remote
Start”.
MSC link operation
The DSE8661 and DSE8x10 modules are in Auto Mode .