Introduction
Page 7 of 146 057-259 ISSUE: 1
1 INTRODUCTION
This document details the installation and operation requirements of the DSE8660 MKII module and is
part of the DSE
Genset® range of products.
The manual forms part of the product and should be kept for the entire life of the product. If the
product is passed or supplied to another party, ensure that this document is passed to them for
reference purposes.
This is not a controlled document. DSE do not automatically inform on updates. Any future updates of
this document are included on the DSE website at www.deepseaplc.com
The DSE86xx MKII series is designed to provide differing levels of functionality across a common
platform. This allows the generator OEM greater flexibility in the choice of controller to use for a
specific application.
The DSE8660 MKII module is designed to provide differing levels of functionality across a common
platform. This allows the generator OEM greater flexibility in the choice of controller to use for a
specific application.
Synchronsing and Load Sharing features are included within the controller, along with the necessary
protections for such a system.
The user also has the facility to view the system operating parameters via the text LCD display.
The DSE8660 MKII module has been designed to monitor the mains (utility) supply and automatically
start/stop one or more generator sets equipped with DSE8610 MKII controllers depending upon the
status of the mains (utility) supply.
The powerful ARM microprocessor contained within the module allows for incorporation of a range of
complex features:
Text based LCD display
True RMS Voltage
Current and Power monitoring
USB, RS232, RS485 and Ethernet Communications
Fully configurable inputs for use as alarms or a range of different functions.
Synchronising and load sharing with load demand start/stop
Integral PLC to help provide customisation where required
Data Logging
R.O.C.O.F. and vector shift protection for detection of mains failure when in parallel with the mains.
The DSE Configuration Suite PC Software allows alteration of selected operational sequences,
timers, alarms and operational sequences. Additionally, the module’s integral front panel configuration
editor allows adjustment of this information.
Access to critical operational sequences and timers for use by qualified engineers, can be protected
by a security code. Module access can also be protected by PIN code. Selected parameters can be
changed from the module’s front panel.
The module is housed in a robust plastic case suitable for panel mounting. Connections to the module
are via locking plug and sockets.