7.2 ‘RUNNING’ CONFIGURATION EDITOR
7.2.1 ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
• The Running Editor is enterable whilst the generator is running. All protections remain active
when the generator is running while the Running Editor is entered
• Press and hold the Tick button to access the Running Editor.
7.2.2 ENTERING PIN
NOTE: The PIN is not set by DSE when the module leaves the factory. If the module has a
PIN code set, this has been affected by your engine supplier who should be contacted if you
require the code. If the code has been ‘lost’ or ‘forgotten’, the module must be returned to the
DSE factory to have the module’s code removed. A charge is made for this procedure.
NB - This procedure cannot be performed away from the DSE factory.
NOTE: The PIN is automatically reset when the editor is exited (manually or automatically)
to ensure security.
Even if a module security PIN has been set, the PIN is not requested whilst entering the Running
Editor.
7.2.3 EDITING A PARAMETER
NOTE: Pressing and holding the Menu Navigation buttons provides the auto-repeat
functionality. Values can be changed quickly by holding the navigation buttons for a
prolonged period of time.
• Press the Right or Left buttons to cycle to the section to view/change.
• Press the Up or Down buttons to select the parameter to view/change within the currently
selected section.
• To edit the parameter, press the Tick button to enter edit mode. The parameter begins to
flash to indicate editing.
• Press the Up or Down buttons to change the parameter to the required value.
• Press the Tick button to save the value. The parameter ceases flashing to indicate that it
has been saved.