Minimum Sets Not Reached
On start up, If the number of available generators on the MSC link
has not achieved the Minimum Number of Sets Not Reached value
before the end of the timer, the LCD indicates Minimum Number of
Sets Not Reached.
MSC Alarms Inhibited
had become active disabling all the MSC alarms.
MSC Data Error
The module detected that data on the MSC link had become corrupt,
possibly caused by incorrect wiring or faulty cabling.
MSC Failure
That module detected that the MSC communication failed, most
likely caused by it being disconnected.
MSC Too Few Sets
That module detected that the number of modules on the MSC was
less then the configured Minimum Modules on MSC Link setting.