Mains ROCOF
The module detected that the mains frequency had changed at a
rate larger then the Mains ROCOF Alarm Trip level when the
generator was in parallel with the mains.
Mains Under Positive
Sequence
The module detected the mains voltage positive sequence had fallen
below the configurable Trip level for the configured delay timer.
Mains Vector Shift
The module detected that the mains voltage waveform’s vector had
shifted more then the Mains Vector Shift Alarm Trip level when the
generator was in parallel with the mains.
MSC Failure
That module detected that the MSC communication failed, most
likely caused by it being disconnected.
MSC ID Error
The module detected that another module on the MSC link had the
same GenSet MSC ID configured.
MSC Old Version Unit
The module detected that another module on the MSC link was
incompatible. Check all the module firmware version numbers
(under About | Application Number on the modules’ displays) and
ensure all are the latest version firmware. Use the DSE
Configuration Suite Software to upgrade the firmware (Tools |
Update Firmware) of the older modules.
MSC Too Few Sets
That module detected that the number of modules on the MSC was
less then the configured Minimum Modules on MSC Link setting.
Out Of Sync Bus
NOTE: For further details, refer to DSE Publication:
056-047 Out of Sync and Failed to Close Training Document.
If the module detects that the generator bus supply is not sync when
the breaker is closed. The LCD indicates Out Of Sync Bus.
Out of Sync Mains
NOTE: For further details, refer to DSE Publication:
056-047 Out of Sync and Failed to Close Training Document.
If the module detects that the mains supply is not sync when the
breaker is closed. The LCD indicates Out Of Sync Mains.
Priority Selection Error
If the module detects that another DSE8660 MKII shares the same
priority number, an electrical trip is initiated. The LCD indicates
Priority Selection Error.