Next steps
Replace the CBB cold plate module for Intel GPU configurations.
Installing the CBB cold plate module for Intel GPU configurations
Prerequisites
1. Follow the safety guidelines listed in the Safety instructions.
2. Follow the procedure listed in the Before working inside your system .
3. Remove the storage tray.
4. Remove the risers.
5. Remove the VSB cables from the system board.
6. Disconnect all the cables from the system board and make note of all the cable connections. For more information, see
Cabling diagram.
7. Remove lower brace cover.
8. Disconnect the liquid cooling tubes 11 and 12 from the Manifold for DLC module and keep in on the system board and make
sure do not damage any connectors on the system board.
9. Slide out the system board tray.
Steps
1. Here is the orientation image for removal and installation sequence of liquid cooling tubes for processor, CBB, GPU cold
plates.
Figure 171. Removal and installation sequence of liquid cooling tubes for processor, CBB, GPU cold plates
2. If you are using an existing GPU cold plate, follow the below process to install the thermal paste on the GPU cold plate.
182
Installing and removing system components