Revision 2016/03, 6ELE, V1.14
4-83
09.05
Reserved
09.06 Reserved
09.07
Response Delay Time Unit: 2ms
Settings 0 ~ 200 (400msec) Factory Setting: 1
This parameter is the response delay time after AC drive receives communication command as shown in
the following. 1 unit = 2 msec.
RS485 BUS
PC command
Handling time
of AC drive
Response Delay Time
Response Message of AC Drive
Max.: 6msec
Pr.09.07
09.08
KPC-CC01 Keypad Enable / Disable
Settings 0: Disable Factory Setting: 0
1: Enable
When Pr09-08-1, the communication formats are 19200, RTU, 8, N, 2
When using PU06, Pr09.01, Pr09.04 and Pr09.08 are disabled.
When Pr09.08=1, the communication formats are 19200, RTU, 8, N,.2. Pr09.01. Pr09.04 are also disabled