Chapter 4 Parameters|
||
|
4-100 Revision 2016/03, 6ELE, V1.14
Related Parameters when Pr10.35=2
Parameter
Function Setting
Setting
user’s
master
user’s
slave
Note
00.03
Start-up Display
Selection
0: Display the frequency command value
(Fxxx)
0 3 3
1: Display the actual output frequency
(Hxxx)
2: Display the content of user-defined unit
(Uxxx)
3: Multifunction display, see Pr.00.04
4: FWD/REV command
00.04
Content of Multi-
function Display
0: Display the content of user-defined unit
(Uxxx)
0 8 8
1: Display the counter value (c)
2: Display the status of multi-function
input terminals (d)
3: Display DC-BUS voltage (u)
4: Display output voltage (E)
5: Display PID analog feedback signal
value (b) (%)
6: Output power factor angle (n)
7: Display output power (P)
8: Display PID setting and feedback
signal
9: Display AVI (I) (V)
10: Display ACI (i) (mA)
11: Display the temperature of IGBT (h)
(°C)
00.13
User-defined
Value
(correspond to
max. operating
frequency)
0 to 9999
0 100 100
Set up the
constant
pressure
control to
to the
largest
physical
quantity
and the
decimal
place. The
current
number
displayed
is 10.0
00.14
Decimal place of
User-defined
Value
0 to 3
0 1 1