Group 8 Special Parameters
Parameter
Explanation Settings
Setting
r
08.00 DC Brake Current Level 0 to 100% 0
08.01
DC Brake Time during
Start-Up
0.0 to 60.0 sec 0.0
08.02
DC Brake Time during
Stopping
0.0 to 60.0 sec 0.0
08.03 Start-Point for DC Brake 0.00 to 599.0Hz 0.00
08.04
Momentary Power Loss
Operation Selection
0: Operation stops after momentary power loss
0
1: Operation continues after momentary power loss,
speed search starts with the Master Frequency
reference value
2: Operation continues after momentary power loss,
speed search starts with the minimum frequency
08.05
Maximum Allowable
Power Loss Time
0.1 to 20.0 sec 2.0
08.06 Base-block Speed Search
0: Disable speed search
1: Speed search starts with last frequency command
2: Starts with minimum output frequency
1
08.07
B.B. Time for Speed
Search
0.1 to 5.0 sec 0.5
08.08
Current Limit for Speed
Search
30 to 200% 150
08.09
Skip Frequency 1 Upper
Limit
0.00 to 599.0 Hz 0.00
08.10
Skip Frequency 1 Lower
Limit
0.00 to 599.0 Hz 0.00
08.11
Skip Frequency 2 Upper
Limit
0.00 to 599.0 Hz 0.00
08.12
Skip Frequency 2 Lower
Limit
0.00 to 599.0 Hz 0.00
08.13
Skip Frequency 3 Upper
Limit
0.00 to 599.0 Hz 0.00
08.14
Skip Frequency 3 Lower
Limit
0.00 to 599.0 Hz 0.00
08.15 Auto Restart After Fault 0 to 10 (0=disable) 0
08.16
Auto Reset Time at
Restart after Fault
0.1 to 6000 sec
60.0
08.17 Auto Energy Saving
0: Disable
0
1: Enable
08.18 AVR Function
0: AVR function enable
0
1: AVR function disable
2: AVR function disable for decel.
3: AVR function disable for stop
08.19 Reserved
08.20
Compensation Coefficient
for Motor Instability
0.0~5.0
0.0
08.21
Level of Pre-heat DC
Current
0~100%
0
08.22
Pre-heat DC Current Duty
Cycle
0~100%
0