Revision 2016/03, 6ELE, V1.14
B-9
B.5 Zero Phase Reactor (RF220X00A)
Dimensions are in millimeter and (inch)
Cable type (Note
Recommended Wire Size
Qty. Wiring Method
AWG mm
2
Nominal (mm
2
)
Single-core
≦
10
≦
5.3
≦
5.5 1 Diagram A
≦
2
≦
33.6
≦
38 4 Diagram B
Three-core
≦
12
≦
3.3
≦
3.5 1 Diagram A
≦
1
≦
42.4
≦
50 4 Diagram B
Note: 600V Insulated unshielded Cable.
Power
Supply
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Power
Supply
MOTOR
Diagram B
Please put all wires through 4
Diagram A
Please wind each wire 4 times around
the core. The reactor must be put at
inverter output as close as possible.