Chapter 4 Parameters|
||
|
4-66 Revision 2016/03, 6ELE, V1.14
If temperature exceeds the motor PTC overheat warning level (Pr.07.15), the drive will act according to
Pr.07.17 and display . If the temperature decreases below the result (Pr.07.15 minus Pr.07.16), the
warning display will disappear.
07.13
Input Debouncing Time of the PTC Protection Unit: 2ms
Settings 0~9999 (is 0-19998ms) Factory Setting: 100
This parameter is to delay the signals on PTC analog input terminals. 1 unit is 2 msec, 2 units are 4 msec, etc.