Chapter 4 Parameters|
||
|
4-104 Revision 2016/03, 6ELE, V1.14
Parameter
Explanation Settings
Factory
Setting
End
user’s
master
End
user’s
slave
Note
10.43
Pump’s error
handling
Bit0: whether to switch to an
alternative pump when operation
pump error occurred.
0: Stop all pump action
1: Switch to an alternative pump
Bit1: Standby or stop after resetting from
error.
0: Standby after reset.
1: Stop after reset.
Bit2: To run a pump or not when an error
is occurred.
0: Do not start.
1: Select an alternate pump.
1
10.44
Selection of pump
startup sequence
0
By pump’s ID #
1
By the running time.
0
10.45
Running time of
multi- pump under
alternative
operation
0.0~360.0 sec 60.0