Chapter 4 Parameters|
||
|
4-20 Revision 2016/03, 6ELE, V1.14
Parameter
Explanation Settings
Factory
Setting
Custome
r
10.43 Pump’s error handling
Bit0: whether to switch to an
alternative pump when operation
pump error occurred.
0: Stop all pump action
1: Switch to an alternative pump
Bit1: Standby or stop after resetting from error.
0: Standby after reset.
1: Stop after reset.
Bit2: To run a pump or not when an error is
occurred.
0: Do not start.
1: Select an alternate pump.
1
10.44
Selection of pump startup
sequence
0
By pump’s ID #
1
By the running time.
0
10.45
Running time of multi- pump
under alternative operation
0.0~360.0 sec 60.0
10.46
~
10.48
Reserved
10.49
Assign the setting of
Pr10.12[PID feedback
level ]
0: Use the current setting (factory setting), verify
if any error by checking feedback deviation,
1: Set low water pressure percentage (%),
verify if any error by checking physical quantity
value’s feedback.
0
10.50
Number of times to restart
when PID Error is occurred.
0~1000 times 0

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta Electronics VFD-EL series and is the answer not in the manual?

Delta Electronics VFD-EL series Specifications

General IconGeneral
BrandDelta Electronics
ModelVFD-EL series
CategoryMedia Converter
LanguageEnglish

Related product manuals