Oil Temperature Setpoints
The OIL TEMPERATURE SETPOINTS screen allows the operator to set acceptable ranges for the
RECIP oil temperature.
The following table lists the data entry fields and a description of their purposes.
TERM DEFINITION RANGE
HIGH FAILURE The compressor will be failed (stopped) when
the oil temperature exceeds this value. 32 - 392 DEGF
HIGH ALARM The Viltech will report an alarm to the operator
when the oil temperature exceeds this value 32 - 392 DEGF
HEATER CONTROL The temperature at which to maintain the oil in
the separator. The oil heater uses the Oil
Temperature sensor but only when the compressor
is stopped. 32 - 392 DEGF
LOW ALARM The Viltech will report an alarm to the operator when
the Oil Temperature is below this value. 32 - 392 DEGF
LOW FAILURE The compressor will be failed (stopped) when the
Oil Temperature is below this value. 32 - 392 DEGF
Oil Temperature Setpoints Screen
Oil Temperature Definitions