Intermediate Temperature Setpoints (Two Stage only)
The INTERMEDIATE TEMPERATURE SETPOINTS screen is only visible on a Two Stage compressor.
The following table lists the parameters displayed on the Process Temperature Setpoints screen.
TERM DEFINITION RANGE
HIGH FAILURE A failure is reported and the compressor is shutdown when the Intermediate
Temperature rises above the High Failure setpoint 32 - 392 DEGF
HIGH ALARM An alarm is reported when the Intermediate Temperature rises above the
High Alarm setpoint. 32 - 392 DEGF
LOW ALARM An alarm is reported when the Intermediate Temperature falls below the low
alarm setpoint. 32 - 392 DEGF
LOW FAILURE An failure is reported and the compressor is shutdown when the Intermediate
Temperature falls below the low failure setpoint. 32 - 392 DEGF
Intermediate Temperature Setpoints
Intermediate Temperature Active Definitions