3 Transducer Block Device Functions Proline Promass 83 FOUNDATION Fieldbus
126 Endress+Hauser
Press.Corr. -
Pressure
AUTO - OOS
! Note!
The entry is not active unless the FIX option was selected in the "Press.Corr.
- Pressure Mode" parameter.
Use this parameter to enter the value for the process pressure which should
be used during pressure correction.
User input:
7-digit floating-point number
Factory setting:
0 bar g
! Note!
The associated unit is taken from the "System Units" parameter group.
Sys. - Install.
Direction
Sensor
AUTO - OOS Use this parameter to reverse the sign of the flow quantity, if necessary.
! Note!
Ascertain the actual direction of fluid flow with reference to the direction
indicated by the arrow on the sensor (nameplate).
Options:
NORMAL (flow as indicated by the arrow)
INVERSE (flow opposite to direction indicated by the arrow)
Factory setting:
NORMAL
Sys. - Density
Damping
AUTO - OOS The density filter allows the sensitivity of the density measuring signal to be
lowered with respect to variations in the density of the fluid, e.g. with
inhomogeneous liquids. The damping acts on all parameters and outputs of
the measuring device.
User input:
Max. 5-digit number, including unit: 0.00 to 100.00 s
Factory setting:
0.00 s
Sys. - Flow Damping AUTO - OOS Setting the filter depth of the digital filter. The sensitivity of the flow
measurement signal can be reduced with respect to interference peaks
(e.g. in the event of a high solid content, gas bubbles in the fluid etc.). The
reaction time of the measuring device increases with every increase in the
filter setting. The damping acts on all parameters and outputs of the
measuring device.
User input:
0 to 100 s
Factory setting:
0 s
"Flow" Transducer Block / base index 1400:
Parameter
Write access
with operating
mode
(MODE_BLK)
Description