ero electronic MKP - PID Group at the End of Program 1; Program 1 - Timer Event 1 - Step 1; Set Point at the End of Program 1

Default Icon
172 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
120
Gr. PGr. P
Gr. PGr. P
Gr. P
from -100.0 to 100.0 % if the devices is configured with
two control outputs (split range excluded).
- Set point at the end of program 1 - [r.A16]- Set point at the end of program 1 - [r.A16]
- Set point at the end of program 1 - [r.A16]- Set point at the end of program 1 - [r.A16]
- Set point at the end of program 1 - [r.A16]
This parameter is available only when the selected program is
not running, it is not a linked program and "Control type at the
end of the program 1" [r.A14] is equal to ñSP.
Upper display: Pr.xx where xx is the number of the selected
program
Range:from rL (set point low limit [rE.12]) to rH set point high
limit [rE.13]).
- PID group at the end of program 1 - [r.A17]- PID group at the end of program 1 - [r.A17]
- PID group at the end of program 1 - [r.A17]- PID group at the end of program 1 - [r.A17]
- PID group at the end of program 1 - [r.A17]
This parameter can be modified only when the selected
program is not running, it is not a linked program and at least
one control output is configured.
Upper display: Pr.xx where xx is the number of the selected
program
Range:from 0 to 5
NOTENOTE
NOTENOTE
NOTE: setting ñPID equal to 0, the instrument will
maintain the PID values selected for the last program
segment.
- Program 1 - Timer event 1 - Step 1 - [r.A18]- Program 1 - Timer event 1 - Step 1 - [r.A18]
- Program 1 - Timer event 1 - Step 1 - [r.A18]- Program 1 - Timer event 1 - Step 1 - [r.A18]
- Program 1 - Timer event 1 - Step 1 - [r.A18]
This parameter can be modified only when the selected
program is not running, it is not a linked program and the
specific timer event is configured.
Upper display: On.h or On.ñ
where
On shows that during the first step the
relative output will be in ON
condition;
h shows that the time base is
expressed in hours and minutes;
ñ shows that the time base is
expressed in minutes and seconds.
NOTENOTE
NOTENOTE
NOTE: the time base of the timer event is equal to the "soak
time eng. unit" selection [r.A02].
Lower display: t.xx.y
where
xx shows the event number
y shows the step number
Range:from 0 to 99.59
Above this value the display will show "End" and this
step and all the next steps are deleted and the timed
event is ended.
XKP-1-D1.pmd 25/05/2006, 11.28120