78
Gr. 4Gr. 4
Gr. 4Gr. 4
Gr. 4
Run time group 4 [r.dxx]Run time group 4 [r.dxx]
Run time group 4 [r.dxx]Run time group 4 [r.dxx]
Run time group 4 [r.dxx]
CONTROL PARAMETERS
NOTENOTE
NOTENOTE
NOTE: when SMART function is activated, all the Group 4
parameters cannot be modified.
- Proportional band - [r.d01]- Proportional band - [r.d01]
- Proportional band - [r.d01]- Proportional band - [r.d01]
- Proportional band - [r.d01]
This parameter is available when at least one control output is
configured.
Range: from 0.5% to 999.0% of the input span.
Set 0.0% for On/OFF control action
NOTESNOTES
NOTESNOTES
NOTES:
1) The Pb resolution will be equal to 0.1% up to 10.0% and 1%
up to 999.0.
2) When device is working with SMART algorithm the “Pb”
value will be limited as selected by parameters “Pb.Hi”
[r.M02] and “Pb.Lo” [r.M01].
- Hysteresis (for ON/OFF control) - [r.d02] - Hysteresis (for ON/OFF control) - [r.d02]
- Hysteresis (for ON/OFF control) - [r.d02] - Hysteresis (for ON/OFF control) - [r.d02]
- Hysteresis (for ON/OFF control) - [r.d02]
This parameter is available when Pb [r.d01]=0 (On/OFF control
action)
Range: from 0.1% to 10.0% of the input span.
- Integral time - [r.d03] - Integral time - [r.d03]
- Integral time - [r.d03] - Integral time - [r.d03]
- Integral time - [r.d03]
This parameter is available when at least one control output is
configured and Pb [r.d01] is different from 0.
Range: from 00.01 to 20.00 mm.ss
Above this value the display blanks and the integral
action is excluded
NOTENOTE
NOTENOTE
NOTE: When device is working with SMART algorithm the “ti”
value will be limited as selected by “ti.Hi” [r.M04] and “ti.Lo”
[r.M03].
- Derivative time - [r.d04]- Derivative time - [r.d04]
- Derivative time - [r.d04]- Derivative time - [r.d04]
- Derivative time - [r.d04]
This parameter is available when at least one control output is
configured, “Cn.tP” [C.G02] is equal to “Pid” and "Pb" [r.d01] is
different from 0.
Range: From 00.00 to 10.00 mm.ss
XKP-1-D1.pmd 25/05/2006, 11.2878