EasyManua.ls Logo

ero electronic MKP - Decimal Point Position; Read-Out- Initial Scale Value; Square Root Extraction for Main Input

Default Icon
172 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
33
CnF. 1CnF. 1
CnF. 1CnF. 1
CnF. 1
2) When the square root extraction is enabled the values of the
following parameters:
- "ñ.In.L" (read-out - initial scale value [C.d05]),
- "ñ.In.H" (read-out - full scale value [C.d06]),
- "brG.L" (bargraph - initial scale value [C.I03]),
- "brG.H" (bargraph - full scale value [C.I04])
- "SS.th" (threshold to enable the soft start [C.I09])
must be positive or equal to zero.
Enabling the square root extraction the instrument verifies
the current value of the "ñ.In.L", "ñ.In.H", "brG.L", "brG.H"
and "SS.th" parameters and force to zero the eventual
negative values.
-
Read-out- initial scale value - [C.d05]Read-out- initial scale value - [C.d05]
Read-out- initial scale value - [C.d05]Read-out- initial scale value - [C.d05]
Read-out- initial scale value - [C.d05]
Ranges: -from -1999 to 9999 for linear input (Input range 31 to
38),
- from 0 to 9999 for linear input with square root
extraction,
- from initial range value to "ñ.In.H" (read-out- full
scale value C.d06]) for TC/RTD input
NOTESNOTES
NOTESNOTES
NOTES:
1) The Read-out initial scale value can be higher than the
Read-out - full scale value.
- Decimal point position - [C.d03]- Decimal point position - [C.d03]
- Decimal point position - [C.d03]- Decimal point position - [C.d03]
- Decimal point position - [C.d03]
Ranges:
----. = no decimal figure
---.- = one decimal figure
--.-- = two decimal figures
-.--- = three decimal figures
NOTESNOTES
NOTESNOTES
NOTES:
1) For main input type 1 to 6, 15 and 30 only the "no decimal
figure" and "one decimal figure" are selectable, the input
range is limited within -199.9 and 999.9 and it acts as an
input type changement.
2) For main input type 7 to 14 and 16 to 29 this parameter is
not available.
3) For linear input types (from 31 to 38) all positions are
available.
- Square root extraction for main input -- Square root extraction for main input -
- Square root extraction for main input -- Square root extraction for main input -
- Square root extraction for main input -
[C.d04][C.d04]
[C.d04][C.d04]
[C.d04]
Ranges: dIS = square root extraction disabled
Enb = square root extraction enabled
NOTESNOTES
NOTESNOTES
NOTES:
1) This parameter is available only for main input type 31 to 38.
XKP-1-D1.pmd 25/05/2006, 11.2833

Table of Contents