- Alarm 4 type - [r.F13]- Alarm 4 type - [r.F13]
- Alarm 4 type - [r.F13]- Alarm 4 type - [r.F13]
- Alarm 4 type - [r.F13]
This parameter is available only when OUT 4 is configured as
alarm 4 output (“O4.Fn” [C.E04] = “ALr.4”)
Range:Proc = Alarm on process variable
bAnd = Band alarm on process variable
dEV = Deviation alarm on process variable
ñAin = Alarm on Main control output value
SECn= Alarm on Secondary control output value
NOTENOTE
NOTENOTE
NOTE: When alarm type has been changed the alarm
threshold will be forced to its default value and alarm status will
be deleted.
- Alarm 4 configuration - [r.F14]- Alarm 4 configuration - [r.F14]
- Alarm 4 configuration - [r.F14]- Alarm 4 configuration - [r.F14]
- Alarm 4 configuration - [r.F14]
This parameter is available only when OUT 4 is configured as
alarm 4 output (“O4.Fn” [C.E04] = “ALr.4”)
Range: H.A. = High alarm (outside band) with automatic
reset
L.A. = Low alarm (inside band) with automatic reset
H.A.Ac= High alarm (outside band) with automatic
reset and acknowledge
L.A.Ac= Low alarm (inside band) with automatic reset
and acknowledge
H.L. = High alarm (outside band) with manual reset
L.L. = Low alarm (inside band) with manual reset
NOTENOTE
NOTENOTE
NOTE: When alarm configuration has been changed, the alarm
status will be deleted.
- Alarm 4 action - [r.F15]- Alarm 4 action - [r.F15]
- Alarm 4 action - [r.F15]- Alarm 4 action - [r.F15]
- Alarm 4 action - [r.F15]
This parameter is available only when OUT 4 is configured as
alarm 4 output (“O4.Fn” [C.E04] = “ALr.4”)
Range: dir = direct action (Relay energized or SSr=1 in
alarm condition)
rEV = Reverse action (Relay energized or SSr=1 in
non alarm condition)
- Alarm 4 stand-by (mask) function - [r.F16]- Alarm 4 stand-by (mask) function - [r.F16]
- Alarm 4 stand-by (mask) function - [r.F16]- Alarm 4 stand-by (mask) function - [r.F16]
- Alarm 4 stand-by (mask) function - [r.F16]
This parameter is available only when OUT 4 is configured as
alarm 4 output (“O4.Fn” [C.E04] = “ALr.4”)
Range:OFF = Stand-by function disabled
On = Stand-by function enabled
NOTESNOTES
NOTESNOTES
NOTES:
1) If the alarm is programmed as band or deviation alarm, this
function masks the alarm condition after a set point change
or at the instrument start-up until process variable reaches