87
Gr. 6Gr. 6
Gr. 6Gr. 6
Gr. 6
Run time group 6 [r.Fxx]Run time group 6 [r.Fxx]
Run time group 6 [r.Fxx]Run time group 6 [r.Fxx]
Run time group 6 [r.Fxx]
ALARM SETTING
- Alarm 1 type - [r.F01]- Alarm 1 type - [r.F01]
- Alarm 1 type - [r.F01]- Alarm 1 type - [r.F01]
- Alarm 1 type - [r.F01]
This parameter is available only when OUT 1 is configured as
alarm 1 output (“O1.Fn” [C.E01] = “ALr.1”)
Range:Proc = Alarm on process variable
bAnd = Band alarm on process variable
dEV = Deviation alarm on process variable
ñAin = Alarm on Main control output value
SECn= Alarm on Secondary control output value
NOTENOTE
NOTENOTE
NOTE: When alarm type has been changed the alarm
threshold will be forced to its default value and alarm status will
be deleted.
- Alarm 1 configuration - [r.F02]- Alarm 1 configuration - [r.F02]
- Alarm 1 configuration - [r.F02]- Alarm 1 configuration - [r.F02]
- Alarm 1 configuration - [r.F02]
This parameter is available only when OUT 1 is configured as
alarm 1 output (“O1.Fn” [C.E01] = “ALr.1”)
Range: H.A. = High alarm (outside band) with automatic
reset
L.A. = Low alarm (inside band) with automatic reset
H.A.Ac= High alarm (outside band) with automatic
reset and acknowledge
L.A.Ac= Low alarm (inside band) with automatic reset
and acknowledge
H.L. = High alarm (outside band) with manual reset
L.L. = Low alarm (inside band) with manual reset
NOTENOTE
NOTENOTE
NOTE: When alarm configuration has been changed, the alarm
status will be deleted.