- Program restart tracking band - [C.G08]- Program restart tracking band - [C.G08]
- Program restart tracking band - [C.G08]- Program restart tracking band - [C.G08]
- Program restart tracking band - [C.G08]
This parameter will be available only when "St.Pr" (program
restart after power supply failure [C.G07]) is equal to “Src”.
Range:from 0 to 500 digits.
- Condition for output safety value - [C.G09]- Condition for output safety value - [C.G09]
- Condition for output safety value - [C.G09]- Condition for output safety value - [C.G09]
- Condition for output safety value - [C.G09]
This parameter will be available only when at least one control
output is configured.
Ranges:
- When no output is configured as open loop servomotor
control, "SF.Cn" can be set as follows:
Std. = No safety value (“standard setting” see chapter
ERROR MESSAGES).
Ov.Un= Safety value applied when the instrument
detects an overrange or underrange condition
of the main input.
OvEr = Safety value applied when the instrument detects
an overrange condition of the main input.
Undr = Safety value applied when the instrument
detects an underrange condition of the main
input.
- When the open loop servomotor control is configured,
"SF.Cn" can be set as follows:
Std. = No safety value (“standard setting” see chapter
ERROR MESSAGES).
Cnd.A = When the instrument detects an overrange or
underrange condition of the main input, the
servomotor is driven to its high limit position.
Cnd.b = When the instrument detects an overrange or
underrange condition of the main input, the
servomotor is driven to its low limit position.
Cnd.C= When the instrument detects an overrange or
underrange condition of the main input, the
action on servomotor is the complement of
“standard” setting.
- Output safety value - [C.G10]- Output safety value - [C.G10]
- Output safety value - [C.G10]- Output safety value - [C.G10]
- Output safety value - [C.G10]
This parameter will be available only when "SF.Cn" [C.G09] is
equal to “Ov.Un”, “OvEr” or “Undr”.
Range:
- from 0.0 % to 100.0 % if device is configured with one
control output;
- from -100.0 % to 100.0 % if device is configured with two
control outputs (split range excluded).
CnF. 4CnF. 4
CnF. 4CnF. 4
CnF. 4