- Out failure detection (OFD) - [C.I11]- Out failure detection (OFD) - [C.I11]
- Out failure detection (OFD) - [C.I11]- Out failure detection (OFD) - [C.I11]
- Out failure detection (OFD) - [C.I11]
This parameter will be available only when the option is fitted
and the main and/or the secondary output is configured as time
proportional control output
Range:nonE = Function not used
ñC.On= Set “Fd.Fn” to “ñC.On” when the load under
test is energized during the ON status of the
main output (relay energized or SSR output
status 1).
ñC.OF= Set “Fd.Fn” to “ñC.OF” when the load under
test is energized during the OFF status of the
main output (relay de-energized or SSR output
status 0).
SC.On= Set “Fd.Fn” to “SC.On” when the load under test
is energized during the ON status of the second-
ary output (relay energized or SSR output status
1).
SC.OF= Set “Fd.Fn” to “SC.OF” when the load under test
is energized during the OFF status of the second-
ary output (relay de-energized or SSR output
status 0).
NOTENOTE
NOTENOTE
NOTE: When the option is not fitted the middle display will
show “no.Pr”
- Primary current of the current transformer- Primary current of the current transformer
- Primary current of the current transformer- Primary current of the current transformer
- Primary current of the current transformer
- [C.I12]- [C.I12]
- [C.I12]- [C.I12]
- [C.I12]
This parameter will be available only when “Fd.Fn” [C.I11] is
different from “nonE”
Range: From 10 A to 100 A
- Out failure detection - output assignment- Out failure detection - output assignment
- Out failure detection - output assignment- Out failure detection - output assignment
- Out failure detection - output assignment
- C.I13- C.I13
- C.I13- C.I13
- C.I13
This parameter will be available only when “Fd.Fn” [C.I11] is
different from “nonE”
Range:nonE = The "Out failure detection" alarm is signalled
only on display
OUt.1 = The "Out failure detection" alarm is signalled
on OUT 1
OUt.2 = The "Out failure detection" alarm is signalled
on OUT 2
OUt.3 = The "Out failure detection" alarm is signalled
on OUT 3
OUt.4 = The "Out failure detection" alarm is signalled
on OUT 4
NOTENOTE
NOTENOTE
NOTE: "Out failure detection "alarm annunciator cannot be
assigned to an output already configured as control output.
XKP-1-D1.pmd 25/05/2006, 11.2864