32
CnF. 1CnF. 1
CnF. 1CnF. 1
CnF. 1
8= TC S From - 50 to 1760 °C
9= TC R From - 50 to 1760 °C
10= TC B From 0 to 1820 °C
11= TC G (or W) From 0 to 2300 °C
12= TC D (or W3) From 0 to 2300 °C
13= TC C (or W5) From 0 to 2300 °C
14= TC Ni-Ni18%Mo From 0 to 1100 °C
* 15= RTD Pt100 From -200 to 850 °C
16= TC L From -150 to 1650 °F
17= TC J From -150 to 1830 °F
18= TC K From -150 to 2500 °F
19= TC T From -330 to 750 °F
20= TC U From -330 to 1110 °F
21= TC E From -150 to 1470 °F
22= TC N From -150 to 2550 °F
23= TC S From - 60 to 3200 °F
24= TC R From - 60 to 3200 °F
25= TC B From 32 to 3300 °F
26= TC G ( or W) From 0 to 4170 °F
27= TC D (or W3) From 0 to 4170 °F
28= TC C (or W5) From 0 to 4170 °F
29= TC Ni-Ni18%Mo From 0 to 2000 °F
* 30= RTD Pt100 From -330 to 1560 °F
31= Linear From 0 to 20 mA
32= Linear From 4 to 20 mA
33= Linear From 0 to 5 V
34= Linear From 1 to 5 V
35= Linear From 0 to 10 V
36= Linear From 2 to 10 V
37= Linear From 0 to 60 mV
38= Linear From 12 to 60 mV
* For these ranges it is possible to select a read-out with one
decimal figure but the instrument could not display a
measure lower than -199.9 or higher than 999.9 and the
input range will be limited by it.
NOTESNOTES
NOTESNOTES
NOTES:
1) When a linear input is selected, the instrument automatically
sets the "readout initial scale value" [C.d05] equal to 0 and
the "readout full scale value" [C.d06] equal to 4000
2) When input type has been changed, the instrument
automatically forces:
- the "ñ.In.L" [C.d05], "SS.th" [C.I09] and "brG.L" [C.I03]
parameters to the new initial scale value,
- the "ñ.In.H" [C.d06] and "brG.H" [C.I04] parameter to the
new full scale value and
- the "ñ.In.d" [C.d03] parameter to "no decimal figure".
XKP-1-D1.pmd 25/05/2006, 11.2832