14. SYSTEM FUNCTIONALITY/CONFIGURATIONS
14.1 OPERATING MODE
The operating modes that can be activated from the SDK EVO are
as follows:
Selection is carried out by pressing the keys on the fixed part of the
programmer; the function is identified by the corresponding symbol
switching on.
- NIGHT
The door closes and motor block is activated (if present). The internal
and external radar are disabled.
The Key control causes opening and closing again after the night-
time pause time.
- MANUAL
The sliding leaves are free and may be manually operated.
- AUTOMATIC
The door opens (partially or totally) then closes again after the set
pause time (default 2 sec.).
Pause time adjustment from 0 to 30 sec.
- DOOR OPEN
The door opens and remains open.
- TWO-DIRECTION AUTOMATIC
Pedestrian transit occurs in both directions; the internal and external
radars are enabled.
- ONE-DIRECTION AUTOMATIC
;
The pedestrian transit way opens in one direction only
(EXIT ONLY ) the external radar is disabled.
(ENTRY ONLY ) the internal radar is disabled.
- TOTAL OPENING
100%
The door opens fully.
- PARTIAL OPENING
%
The door performs reduced openings (default 20%).
Adjustment from 20% to 95% of total opening with 5% steps.
Function Door Status Internal Sensor External Sensor KEY
MANUAL
-------- no effect no effect no effect
TOTALLY OPEN
100%
OPEN no effect no effect no effect
TOTAL TWO-DIRECTION AUTOMATIC
100%
OPEN pause counting restarts pause counting restarts pause counting restarts
CLOSED
total opening and closure again
after pause time
total opening and reclosing
after the pause time
total opening and reclosing
after the pause time
PARTIAL TWO-DIRECTION AUTOMATIC
%
PARTIAL
OPENING
pause counting restarts pause counting restarts pause counting restarts
CLOSED
partial opening and closure again
after pause time
partial opening and reclosing
after the pause time
partial opening and closure again
after pause time
AUTOMATIC ONE-DIRECTIONAL
TOTAL (EXIT ONLY)
100%
OPEN pause counting restarts no effect pause counting restarts
CLOSED
total opening and closure again
after pause time
no effect
total opening and reclosing
after the pause time
AUTOMATIC ONE-DIRECTIONAL
PARTIAL (EXIT ONLY)
%
PARTIAL
OPENING
pause counting restarts no effect pause counting restarts
CLOSED
partial opening and closure again
after pause time
no effect
partial opening and closure again
after pause time
TOTAL ONE-DIRECTIONAL AUTOMATIC (ENTRY ONLY)
100%
OPEN no effect pause counting restarts pause counting restarts
CLOSED no effect
total opening and reclosing
after the pause time
total opening and reclosing
after the pause time
AUTOMATIC ONE-DIRECTIONAL
PARTIAL (ENTRY ONLY)
%
PARTIAL
OPENING
no effect pause counting restarts pause counting restarts
CLOSED no effect
partial opening and reclosing
after the pause time
partial opening and closure again
after pause time
NIGHT
CLOSED no effect no effect
total opening and closure again
after night pause time
PARTIAL NIGHT-TIME
%
CLOSED no effect no effect
partial opening and closure again
after night pause time
PARTIAL OPENING
%
PARTIAL
OPENING
no effect no effect no effect