Versiv Series Cabling Certification Product Family
Users Manual
162
1-7 To enter the length of the test reference cords you will add to
connect to the link, tap TRC LENGTH on the SET REFERENCE
screen. The length you enter does not change the test results.
The tester saves the length with the results to meet TIA
reporting requirements.
1-8 Tap SET REFERENCE.
If reference values are unacceptable, you can use the
FiberInspector probe to inspect connectors. To turn on the
probe, press the button on the probe. To go back to the
reference screen, tap .
1-9 If you did not use the connection wizard, go to step 3.
Step 2: Measure the Loss of the Test Reference Cord You
Will Add
WCaution
If you disconnected a test reference cord from the
output of the tester or remote, you must set the
reference again to make sure your measurements
are reliable.
2-1 On the SET REFERENCE screen, when the reference procedure
is completed, tap NEXT.
2-2 Disconnect the test reference cords from the INPUT ports on
the tester and remote, then use test reference cords and
adapters to make the connections to verify the TRCs, as shown
on the screen and in Figure 61.
2-3 Tap TRC VERIFICATION. The tester measures and saves the loss
of the test reference cords you added. The IDs for these results
start with “TRC”, show the date and time of the test, and have
an for the test result.
The tester shows a warning if the loss of a TRC is more than
these limits: