Versiv Series Cabling Certification Product Family
Users Manual
302
PASS/FAIL Result for Edited Events
When you change a loss event’s type, the tester changes the loss
limit for the event and recalculates the event’s results and the
overall results. The recalculations can possibly change the PASS/
FAIL results. For example (refer to Figure 115):
• You test a link and see a Loss event that has a loss of 0.53 dB.
This causes a FAIL result because the limit for a loss event is
0.30 dB.
• You change the event to an APC Connector. Because the
selected test limit has a loss limit of 0.75 dB for connectors,
the result for the event changes to a PASS
• If the loss event was the only FAIL result on the link, the
overall result will also change from FAIL to PASS.
www.GlobalTestSupply.com
Find Quality Products Online at: sales@GlobalTestSupply.com