Versiv Series Cabling Certification Product Family
Users Manual
176
Step 1: Set the Reference in Far End Source Mode
1-1 Turn on the tester and source let them sit for a minimum of
5 minutes. Let them sit longer if they are above or below
ambient temperature, or if the instructions for the source
specify a longer time.
1-2 Make sure that the home screen shows the correct settings for
the job, and the test type is Far End Source.
To make sure that other settings are correct, tap the test
setup panel, make sure the correct test is selected on the
CHANGE TEST screen, then tap EDIT to see more settings.
Table 7 on page 151 describes the settings.
1-3 Clean and inspect the connectors on the tester, source, and test
reference cords.
1-4 On the home screen tap SET REF.
1-5 In the TEST MODE window, select Auto CertiFiber Pro or the
type of source you will use, then tap DONE.
1-6 On the SET REFERENCE screen, tap RUN WIZARD.
Notes
To only set the reference, and not measure the
loss of your test reference cord, tap SKIP WIZARD
on the SET REFERENCE screen.
Fluke Networks recommends that you measure
the loss of your test reference cord each time you
set the reference.