Certify Fiber Cabling
Autotest in Smart Remote Mode
163
Maximum loss for multimode TRCs: 0.15 dB
Maximum loss for single-mode TRCs: 0.25 dB
If the tester shows a warning, clean and inspect the
connectors on the TRCs in the path that has too much loss,
make sure the cords are straight as shown in Figure 61, then
do the TRC verification again.
Step 3: Do an Autotest in Smart Remote Mode
WCaution
If you disconnected a test reference cord from the
output of the tester or remote, you must set the
reference again to make sure your measurements
are reliable.
3-1 On the SET REFERENCE screen, when the set reference or
TRC verification procedure is completed, tap NEXT to see
how to connect to the link under test.
3-2 Clean and inspect all the connectors.
3-3 Make the connections to do the test on the fiber link, as shown
on the screen and in Figure 61, then tap HOME.
3-4 Tap TEST on the main tester or press on the main or
remote tester.
If the CHECK FIBER CONNECTIONS screen shows an open
fiber:
Make sure that all connections are good and no fibers
have damage. Use the VFL to make sure the fibers in the
link have continuity.
Make sure that the remote is on.
Switch the connections at one end of the patch panel.
(continued)